What are the Steps in Circuit Breaker Testing?

Kind Tests of circuit breaker


Type examinations are organised with the goal of confirming the capacities and making certain the rated particular of the circuit breaker are exact. Such tests are conducted in the specially built testing research laboratory.

Mechanical Examination– It is mechanical capacity type test entailing the duplicated opening and closing of the breaker. A circuit breaker should close and open at proper rate and do its assigned task and function without any failure.


Thermal Examination– Thermal tests are executed to check the thermal actions of the circuit breakers. As a result of the streaming of rated existing via its pole in a rated problem, the breaker under test undertakes steady-state temperature level increases. The temperature increase for ranked existing ought to not go beyond 40 ° for current less than 800A typical current and 50 ° for typical value of current 800A and above.
Dielectric Examination– These examinations are executed to examine power frequency and impulse voltage hold up against capacity. Power regularity tests are kept on a new circuit breaker; the examination voltage modifications with a breaker rated voltage. In impulse tests, impulse voltage of certain value is utilized to the breaker. For outdoor circuit dry and damp examinations are conducted.
Brief -Circuit Examination– Breaker are subjected to unexpected short-circuits in short-circuit test research laboratories, and oscillograms are taken to recognize the behavior of the circuit breakers at the time of switching in, throughout get in touch with splitting and after the arc extinction. The oscillograms are researched with certain referral to the production and damaging currents, both balanced and asymmetrical restriking voltages, and switchgear is in some cases checked at rated conditions.


Regular Examinations of a Breaker


Routine tests are done as per recommendations of standards of Indian Engineering Solution and Indian Standards. These examinations are done on the manufacturers’ premises. Regular examinations verify the proper functioning of the circuit breaker. The routine examinations confirm the correct performance of the breaker. Routine screening does not always include complicated gear in order to ensure that a circuit breaker is functional. Some guidelines and suggestions for these tests consist of routine maintenance and verifying that breaker efficiency remains in line with manufacture’s calibration contours. It is important that these examinations are done under stable problems at appropriate temperature so that there are no variants in the information. A few of the examinations are listed here.

Breaker Journey Examination


By evaluating the current eaten by the trip coil during the circuit breaker’s procedure, it is feasible to figure out whether there are mechanical or electrical concerns present. Oftentimes, such concerns can be localised to assist in finding the origin. Optionally, keeping an eye on the stumbling supply’s voltage during the operation can discover problems occurring with stumbling batteries.

Insulation Resistance Test


For private breaker resistance testing, load and line conductors should be preferably disconnected. If not separated the examination worths will certainly likewise include the qualities of the linked circuit. Resistance testing is vital for verifying that the shielding product which makes up the molded situations breakers are carrying out properly. In order to check for insulation resistance, an instrument called a megger is made use of. A megger instrument applies a known DC voltage to an offered cable for a given amount of time in order to test the resistance within the insulation on that certain cable or winding. It is important that voltage is utilized as the resistance consulted an ohmmeter might vary when there are no record of possible differences. It must also be noted that if you apply a voltage that is expensive for that insulation to withstand, then you can possibly damage the insulation.

Connection Examinations


Connection screening is very important to make certain that an ideal electric connection is available and to recognise traces of overheating represented by colour difference. It is necessary that electrical links are correctly installed to the CB to avoid and minimize overheating.

Get In Touch With Resistance Examination


Typical deterioration of calls within the CB emerges after expanded use. A simple technique to determine traces of deteriorating within the circuit breaker is to quantify the resistance across every pole of the breaker. Indicators of unusual problems within the CB such as erosion and contamination of contacts appear if there are extreme millivolt drops throughout the breaker. The call resistance test is very important in discovering if or not a breaker is still apt for functioning.

Overload Tripping Test


Overload stumbling parts of CBs can be checked by inputting 300% of the breaker score into each pole of the circuit breaker to determine that it will open up automatically. The intention of this is to make sure that the circuit breaker will run or otherwise. Describe NETA standards for trip times that serve for the overload stumbling examination. When looking for out tripping qualities, it is advisable to seek advice from maker’s guidebooks.

Instantaneous Magnetic Tripping


In regular examinations, it pertains to discover that the magnetic feature is practical and will trip the circuit breaker instead of locating the precise value at which the instant magnetic function functions.